EVALUACIÓN DEL DETERIORO POR CORROSIÓN ATMOSFÉRICA EN ESTRUCTURAS DE HORMIGÓN ARMADO EN UNA ZONA COSTERA DE PEDERNALES, MANABÍ ECUADOR.

Saved in:
Bibliographic Details
Title: EVALUACIÓN DEL DETERIORO POR CORROSIÓN ATMOSFÉRICA EN ESTRUCTURAS DE HORMIGÓN ARMADO EN UNA ZONA COSTERA DE PEDERNALES, MANABÍ ECUADOR.
Alternate Title: EVALUATION OF ATMOSPHERIC CORROSION DETERIORATION IN REINFORCED CONCRETE STRUCTURES IN A COASTAL ZONE OF PEDERNALES MANABÍ, ECUADOR.
Authors: Guerrero Zambrano, Jhon Navarino1, Mendoza Loor, Efren Andrés1, Guerra Mera, Juan Carlos1 juan.guerra@utm.edu.ec
Source: Revista CENIC Ciencias Quimicas. 2025, Vol. 56, p81-99. 19p.
Subjects: CORROSION & anti-corrosives, REINFORCED concrete, ULTRASONIC testing, ELECTROLYTIC corrosion, CHLORIDE ions, COASTS, COMPRESSIVE strength
Geographic Terms: ECUADOR
Abstract (English): A study about atmospheric corrosion deterioration evaluation in reinforced concrete structures was carried out in a coastal zone of Pedernales Canton, Manabí province, Ecuador. Ten structures were selected, located at different distances from the coastline. Different tests such as Compressive Strength, Ultrasonic Pulse Velocity, Resistivity, Corrosion current intensity as an indicator of atmospheric corrosion in reinforcement steel, as well as the Concentration of total and soluble chloride ions, were performed in one column of each structure. The results demonstrated the reinforced concrete quality insufficient used in the building, confirmed by the behavior of the Depth and Carbonation constant values, as well as the Concentrations of total and soluble chloride ion, as a function of distance from the coastline increase where the structures were located. Due to the very high values of Corrosion Current Intensity in the reinforcement steel in the reinforced concrete in the selected column the structures were found in its final or residual service life. On the other hand, according to the comparative statistical analysis from the two methods used in the study the results obtained confirmed that Concentration of soluble chloride ions was the fundamental factor in the origin and development of atmospheric corrosion, despite the concrete used in the column presented a high degree of carbonation. Other factors in concrete that successively influenced the atmospheric corrosion of reinforcement steel were the values of Ultrasonic Pulse Velocity, Compressive Strength, Depth and Carbonation constant. Furthermore, the wetting and drying cycle caused by chloride ion concentrations, primarily those soluble in the concrete of the columns, was another influential factor in the atmospheric corrosion of the reinforcement steel in each of the structures. [ABSTRACT FROM AUTHOR]
Abstract (Spanish): Un estudio, basado en evaluar el deterioro por corrosión atmosférica en estructuras de hormigón armado, fue ejecutado en una zona costera del cantón de Pedernales perteneciente a la provincia de Manabí, Ecuador. Para esto, 10 estructuras fueron selecciona das, emplazadas a diferentes distancias desde la línea costera. Diferentes ensayos como Resistencia a la Compresión, Velocidad de Pulso Ultrasónico, Resistividad, Intensidad de Corriente de Corrosión como un indicador de la corrosión atmosférica en el acero de refuerzo, la Concentración de iones cloruro totales y solubles, fueron ejecutados en una columna de cada estructura. Los resultados, permitieron demostrar la calidad insuficiente que presentó el hormigón armado usado en la construcción, confirmado con el comportamiento de los valores de la Profundidad y Constante de carbonatación, así como el de las Concentraciones de iones cloruro totales y solubles, en función del incremento de las distancias desde la línea costera donde fueron emplazadas las estructura s. Se definió, que las estructuras se encontraron en su vida útil última o residual debido a los valores muy elevados de Intensidad de Corriente de Corrosión en el acero de refuerzo en el hormigón armado en la columna seleccionada. Por otra parte, los resultad os obtenidos de acuerdo con el análisis estadístico comparativo a partir de los dos métodos utilizados en el estudio, confirmaron que la concentración de iones cloruro soluble resultó el factor fundamental en el origen y desarrollo de la corrosión atmosférica, a pesar de que el hormigón usado en la columna presentó un grado elevado de carbonatación. Otros factores en el hormigón influyentes en la corrosión atmosférica del acero de refuerzo de forma sucesiva fueron los valores de la Velocidad de Pulso Ultrasónico, la Resistencia a la Compresión, la Profundidad y Constante de Carbonatación. Además, el ciclo de humectación y secado ocurrido por las concentraciones de iones cloruro, principalmente los solubles en el hormigón de las columnas, resultó otro factor influye nte en la corrosión atmosférica del acero de refuerzo en cada una de las estructuras. [ABSTRACT FROM AUTHOR]
Copyright of Revista CENIC Ciencias Quimicas is the property of Centro Nacional de Investigaciones Cientificas and its content may not be copied or emailed to multiple sites without the copyright holder's express written permission. Additionally, content may not be used with any artificial intelligence tools or machine learning technologies. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)
Database: MedicLatina
FullText Links:
  – Type: pdflink
Text:
  Availability: 0
Header DbId: lth
DbLabel: MedicLatina
An: 193789275
AccessLevel: 6
PubType: Academic Journal
PubTypeId: academicJournal
PreciseRelevancyScore: 0
IllustrationInfo
Items – Name: Title
  Label: Title
  Group: Ti
  Data: EVALUACIÓN DEL DETERIORO POR CORROSIÓN ATMOSFÉRICA EN ESTRUCTURAS DE HORMIGÓN ARMADO EN UNA ZONA COSTERA DE PEDERNALES, MANABÍ ECUADOR.
– Name: TitleAlt
  Label: Alternate Title
  Group: TiAlt
  Data: EVALUATION OF ATMOSPHERIC CORROSION DETERIORATION IN REINFORCED CONCRETE STRUCTURES IN A COASTAL ZONE OF PEDERNALES MANABÍ, ECUADOR.
– Name: Author
  Label: Authors
  Group: Au
  Data: <searchLink fieldCode="AR" term="%22Guerrero+Zambrano%2C+Jhon+Navarino%22">Guerrero Zambrano, Jhon Navarino</searchLink><relatesTo>1</relatesTo><br /><searchLink fieldCode="AR" term="%22Mendoza+Loor%2C+Efren+Andrés%22">Mendoza Loor, Efren Andrés</searchLink><relatesTo>1</relatesTo><br /><searchLink fieldCode="AR" term="%22Guerra+Mera%2C+Juan+Carlos%22">Guerra Mera, Juan Carlos</searchLink><relatesTo>1</relatesTo><i> juan.guerra@utm.edu.ec</i>
– Name: TitleSource
  Label: Source
  Group: Src
  Data: <searchLink fieldCode="JN" term="%22Revista+CENIC+Ciencias+Quimicas%22">Revista CENIC Ciencias Quimicas</searchLink>. 2025, Vol. 56, p81-99. 19p.
– Name: Subject
  Label: Subjects
  Group: Su
  Data: <searchLink fieldCode="DE" term="%22CORROSION+%26+anti-corrosives%22">CORROSION & anti-corrosives</searchLink><br /><searchLink fieldCode="DE" term="%22REINFORCED+concrete%22">REINFORCED concrete</searchLink><br /><searchLink fieldCode="DE" term="%22ULTRASONIC+testing%22">ULTRASONIC testing</searchLink><br /><searchLink fieldCode="DE" term="%22ELECTROLYTIC+corrosion%22">ELECTROLYTIC corrosion</searchLink><br /><searchLink fieldCode="DE" term="%22CHLORIDE+ions%22">CHLORIDE ions</searchLink><br /><searchLink fieldCode="DE" term="%22COASTS%22">COASTS</searchLink><br /><searchLink fieldCode="DE" term="%22COMPRESSIVE+strength%22">COMPRESSIVE strength</searchLink>
– Name: SubjectGeographic
  Label: Geographic Terms
  Group: Su
  Data: <searchLink fieldCode="DE" term="%22ECUADOR%22">ECUADOR</searchLink>
– Name: Abstract
  Label: Abstract (English)
  Group: Ab
  Data: A study about atmospheric corrosion deterioration evaluation in reinforced concrete structures was carried out in a coastal zone of Pedernales Canton, Manabí province, Ecuador. Ten structures were selected, located at different distances from the coastline. Different tests such as Compressive Strength, Ultrasonic Pulse Velocity, Resistivity, Corrosion current intensity as an indicator of atmospheric corrosion in reinforcement steel, as well as the Concentration of total and soluble chloride ions, were performed in one column of each structure. The results demonstrated the reinforced concrete quality insufficient used in the building, confirmed by the behavior of the Depth and Carbonation constant values, as well as the Concentrations of total and soluble chloride ion, as a function of distance from the coastline increase where the structures were located. Due to the very high values of Corrosion Current Intensity in the reinforcement steel in the reinforced concrete in the selected column the structures were found in its final or residual service life. On the other hand, according to the comparative statistical analysis from the two methods used in the study the results obtained confirmed that Concentration of soluble chloride ions was the fundamental factor in the origin and development of atmospheric corrosion, despite the concrete used in the column presented a high degree of carbonation. Other factors in concrete that successively influenced the atmospheric corrosion of reinforcement steel were the values of Ultrasonic Pulse Velocity, Compressive Strength, Depth and Carbonation constant. Furthermore, the wetting and drying cycle caused by chloride ion concentrations, primarily those soluble in the concrete of the columns, was another influential factor in the atmospheric corrosion of the reinforcement steel in each of the structures. [ABSTRACT FROM AUTHOR]
– Name: Abstract
  Label: Abstract (Spanish)
  Group: Ab
  Data: Un estudio, basado en evaluar el deterioro por corrosión atmosférica en estructuras de hormigón armado, fue ejecutado en una zona costera del cantón de Pedernales perteneciente a la provincia de Manabí, Ecuador. Para esto, 10 estructuras fueron selecciona das, emplazadas a diferentes distancias desde la línea costera. Diferentes ensayos como Resistencia a la Compresión, Velocidad de Pulso Ultrasónico, Resistividad, Intensidad de Corriente de Corrosión como un indicador de la corrosión atmosférica en el acero de refuerzo, la Concentración de iones cloruro totales y solubles, fueron ejecutados en una columna de cada estructura. Los resultados, permitieron demostrar la calidad insuficiente que presentó el hormigón armado usado en la construcción, confirmado con el comportamiento de los valores de la Profundidad y Constante de carbonatación, así como el de las Concentraciones de iones cloruro totales y solubles, en función del incremento de las distancias desde la línea costera donde fueron emplazadas las estructura s. Se definió, que las estructuras se encontraron en su vida útil última o residual debido a los valores muy elevados de Intensidad de Corriente de Corrosión en el acero de refuerzo en el hormigón armado en la columna seleccionada. Por otra parte, los resultad os obtenidos de acuerdo con el análisis estadístico comparativo a partir de los dos métodos utilizados en el estudio, confirmaron que la concentración de iones cloruro soluble resultó el factor fundamental en el origen y desarrollo de la corrosión atmosférica, a pesar de que el hormigón usado en la columna presentó un grado elevado de carbonatación. Otros factores en el hormigón influyentes en la corrosión atmosférica del acero de refuerzo de forma sucesiva fueron los valores de la Velocidad de Pulso Ultrasónico, la Resistencia a la Compresión, la Profundidad y Constante de Carbonatación. Además, el ciclo de humectación y secado ocurrido por las concentraciones de iones cloruro, principalmente los solubles en el hormigón de las columnas, resultó otro factor influye nte en la corrosión atmosférica del acero de refuerzo en cada una de las estructuras. [ABSTRACT FROM AUTHOR]
– Name: AbstractSuppliedCopyright
  Label:
  Group: Ab
  Data: <i>Copyright of Revista CENIC Ciencias Quimicas is the property of Centro Nacional de Investigaciones Cientificas and its content may not be copied or emailed to multiple sites without the copyright holder's express written permission. Additionally, content may not be used with any artificial intelligence tools or machine learning technologies. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract.</i> (Copyright applies to all Abstracts.)
PLink https://search.ebscohost.com/login.aspx?direct=true&site=eds-live&db=lth&AN=193789275
RecordInfo BibRecord:
  BibEntity:
    Languages:
      – Code: spa
        Text: Spanish
    PhysicalDescription:
      Pagination:
        PageCount: 19
        StartPage: 81
    Subjects:
      – SubjectFull: CORROSION & anti-corrosives
        Type: general
      – SubjectFull: REINFORCED concrete
        Type: general
      – SubjectFull: ULTRASONIC testing
        Type: general
      – SubjectFull: ELECTROLYTIC corrosion
        Type: general
      – SubjectFull: CHLORIDE ions
        Type: general
      – SubjectFull: COASTS
        Type: general
      – SubjectFull: COMPRESSIVE strength
        Type: general
      – SubjectFull: ECUADOR
        Type: general
    Titles:
      – TitleFull: EVALUACIÓN DEL DETERIORO POR CORROSIÓN ATMOSFÉRICA EN ESTRUCTURAS DE HORMIGÓN ARMADO EN UNA ZONA COSTERA DE PEDERNALES, MANABÍ ECUADOR.
        Type: main
  BibRelationships:
    HasContributorRelationships:
      – PersonEntity:
          Name:
            NameFull: Guerrero Zambrano, Jhon Navarino
      – PersonEntity:
          Name:
            NameFull: Mendoza Loor, Efren Andrés
      – PersonEntity:
          Name:
            NameFull: Guerra Mera, Juan Carlos
    IsPartOfRelationships:
      – BibEntity:
          Dates:
            – D: 01
              M: 01
              Text: 2025
              Type: published
              Y: 2025
          Identifiers:
            – Type: issn-print
              Value: 10158553
          Numbering:
            – Type: volume
              Value: 56
          Titles:
            – TitleFull: Revista CENIC Ciencias Quimicas
              Type: main
ResultId 1