Grid synchronised three phase VSI-based hardware emulator to realise low frequency electromechanical oscillations in power systems and their effects on physical distance relay.
Saved in:
| Title: | Grid synchronised three phase VSI-based hardware emulator to realise low frequency electromechanical oscillations in power systems and their effects on physical distance relay. |
|---|---|
| Authors: | Piri, Jayanta1 (AUTHOR) jayanta.piri@gmail.com, Sengupta, Mainak1 (AUTHOR), Bandyopadhyay, Gautam1 (AUTHOR) |
| Source: | Sādhanā: Academy Proceedings in Engineering Sciences. Sep2024, Vol. 49 Issue 3, p1-22. 22p. |
| Subjects: | Frequencies of oscillating systems, Emulation software, Cyber physical systems, Phase-locked loops, Hardware, Oscillations, Pulse width modulation |
| Abstract: | Practical testing of distance relays under power swing conditions is becoming all the more essential. This is in view of the increasing use of power electronic apparatus due to penetration of renewable sources and/or FACTS controllers now-a-days. To perform such practical tests, a hardware platform emulating power system swing occurrences, as caused by electromechanical oscillation of alternators, is necessary. As a first step it is required to model the phenomenon before its implementation. In this paper an analytical small-signal model of the low-frequency electromechanical oscillations in a grid-connected alternator is presented. Off-line simulation-based validation for a Single Machine Infinite Bus (SMIB) system is done. To emulate an open-loop alternator, a prototype of a controlled grid synchronised VSI with AC-side reactor is developed and practically tested. A control scheme is proposed and implemented to emulate the active power swing phenomenon. Effects of machine inertia and initial power angle on the swing characteristics are investigated. In-process estimation of apparent impedances, as seen from the distance relay terminals downstream towards the grid, is done. Principle of estimating the apparent impedance during power swing is presented with corresponding experimental results. Both real-time and off-line simulation results are in close agreement with the experimental results thus establishing the accuracy of the model and the precision of the experiments. [ABSTRACT FROM AUTHOR] |
| Copyright of Sādhanā: Academy Proceedings in Engineering Sciences is the property of Springer Nature and its content may not be copied or emailed to multiple sites without the copyright holder's express written permission. Additionally, content may not be used with any artificial intelligence tools or machine learning technologies. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.) | |
| Database: | Engineering Source |
|
Full text is not displayed to guests.
Login for full access.
|
|
| Abstract: | Practical testing of distance relays under power swing conditions is becoming all the more essential. This is in view of the increasing use of power electronic apparatus due to penetration of renewable sources and/or FACTS controllers now-a-days. To perform such practical tests, a hardware platform emulating power system swing occurrences, as caused by electromechanical oscillation of alternators, is necessary. As a first step it is required to model the phenomenon before its implementation. In this paper an analytical small-signal model of the low-frequency electromechanical oscillations in a grid-connected alternator is presented. Off-line simulation-based validation for a Single Machine Infinite Bus (SMIB) system is done. To emulate an open-loop alternator, a prototype of a controlled grid synchronised VSI with AC-side reactor is developed and practically tested. A control scheme is proposed and implemented to emulate the active power swing phenomenon. Effects of machine inertia and initial power angle on the swing characteristics are investigated. In-process estimation of apparent impedances, as seen from the distance relay terminals downstream towards the grid, is done. Principle of estimating the apparent impedance during power swing is presented with corresponding experimental results. Both real-time and off-line simulation results are in close agreement with the experimental results thus establishing the accuracy of the model and the precision of the experiments. [ABSTRACT FROM AUTHOR] |
|---|---|
| ISSN: | 02562499 |
| DOI: | 10.1007/s12046-024-02528-6 |