SE—Structures and Environment: Dehumidification in Greenhouses by Condensation on Finned Pipes

Saved in:
Bibliographic Details
Title: SE—Structures and Environment: Dehumidification in Greenhouses by Condensation on Finned Pipes
Authors: Campen, J. B.1, Bot, G. P. A.1,2
Source: Biosystems Engineering. Jun2002, Vol. 82 Issue 2, p177. 9p.
Subjects: Climate in greenhouses, Humidity control, Condensation
Abstract: In this study, an experimental dehumidifying system for greenhouses is tested. The system uses finned pipes fixed under the gutter of the greenhouse. The pipes are cooled below the dewpoint of the greenhouse air by cold water. The humid air passes the pipe and fins by natural convection and condensation occurs reducing the humidity in the greenhouse. The performance of the system in relation to its location and dimensions are studied by computational fluid dynamics calculations. The total heat transferred and condensate removed are monitored as a function of the greenhouse conditions. The system removes 40 g of condensate per hour per square metre of greenhouse floor from the humid air sufficient during periods when heating is applied and ventilation is minimized. The heat transferred at the cold surface by condensation is less than one-third of the total heat removed by the system at a relative humidity of 80%. [Copyright &y& Elsevier]
Copyright of Biosystems Engineering is the property of Academic Press Inc. and its content may not be copied or emailed to multiple sites without the copyright holder's express written permission. Additionally, content may not be used with any artificial intelligence tools or machine learning technologies. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)
Database: Engineering Source
Description
Abstract:In this study, an experimental dehumidifying system for greenhouses is tested. The system uses finned pipes fixed under the gutter of the greenhouse. The pipes are cooled below the dewpoint of the greenhouse air by cold water. The humid air passes the pipe and fins by natural convection and condensation occurs reducing the humidity in the greenhouse. The performance of the system in relation to its location and dimensions are studied by computational fluid dynamics calculations. The total heat transferred and condensate removed are monitored as a function of the greenhouse conditions. The system removes 40 g of condensate per hour per square metre of greenhouse floor from the humid air sufficient during periods when heating is applied and ventilation is minimized. The heat transferred at the cold surface by condensation is less than one-third of the total heat removed by the system at a relative humidity of 80%. [Copyright &y& Elsevier]
ISSN:15375110
DOI:10.1006/bioe.2002.0058